Fluke 1760 - Power Factor; Displacement Power Factor Cos Φ

Fluke 1760
106 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1760
Users Manual
3-16
22
htotd
QQQ =
The 3-phase distortion reactive power sum is calculated as
321 LdLdLdsumd
QQQQ ++=
Please note that the quadratic terms in the
d
Q calculation means that
22
sumhsumtotsumd
QQQ
Power factor
For the power factor one of two different formulas can be selected by the user through the
“Options > Power Factor” menu in PQ Analyze.
Formula 1: The sign is taken from the reactive harmonic power therefore giving an
indication about inductive or capacitive characteristic of the load.
h
h
Q
Q
S
P
PF =
Formula 2: The sign is taken from the real power therefore giving the power flow
direction (motor / generator characteristic of the load).
S
P
PF =
The 3-phase power factor sum is calculated as
sumh
sumh
sum
sum
sum
Q
Q
S
P
PF =
or
sum
sum
sum
S
P
PF =
Displacement power factor cos φ
The cos φ is most commonly referred to as the power factor of the fundamental
component. More general there is a cos φ for every harmonic frequency component.
When you select the harmonics analysis in the main analysis window in PQ Analyze you
can display the cos φ for all harmonics including the fundamental.
Harmonics analysis parameter group:
The formula used for calculating the cos φ is:
=
i
i
i
P
Q
arctancoscos
ϕ