EasyManua.ls Logo

Fluke 1760 - Two Star-Connected Voltage Systems

Fluke 1760
106 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation
Connections to Measuring Circuits 3
3-11
Note
If this option (Calculation) is checked, you have to enter the phase-to-phase
voltage as the rated voltage V
N
in ‘Settings – Nominal / Limit Values’ (e.g.
400 V in the 230 V P-N network).
Two Star-Connected Voltage Systems
With this method, you can determine two phase voltages and the respective N conductor
voltages in two star connected three-phase systems.
Figure 3-6 shows the circuit diagram for 2-voltage system with neutral.
Fluke 1760
PEN
L2
L3
L1
L2
L3
L1
N
PE
Mains
System-U-U-Stern.eps
Figure 3-6. Circuit Diagram: 2 Voltage System with Neutral
Associated PC Software Settings:
messsystem2.bmp
Note
The power quality assessment according to EN50160 can be performed for
the phase voltages of system 1 and system 2 respectively; the preset limit
values apply to both evaluations.

Table of Contents

Other manuals for Fluke 1760