789/787B
Users Manual
22
Simulate Mode
Simulate mode is so named because the meter simulates
a current loop transmitter. Use simulate mode when an
external dc voltage of 15 to 48 V is in series with the
current loop under test.
Caution
Set the rotary function switch to one of the
mA output settings BEFORE connecting the
test leads to a current loop. Otherwise, a low
impedance from the other rotary function
switch positions could be presented to the
loop, causing up to 35 mA to flow in the loop.
Simulate mode is selected automatically by inserting the
test leads into the SIMULATE + and jacks as shown in
Figure 2. The arrows show the conventional current flow.
Simulate mode conserves battery life, so use it instead of
source mode whenever possible.
The display looks the same in source and simulate
modes. The way to tell which mode is in use is to see
which pair of output jacks is in use.
Changing the Current Span
The meter’s current output span has two settings (with
overrange to 24 mA):
4 mA = 0 %, 20 mA = 100 % (factory default)
0 mA = 0 %, 20 mA = 100 %
To find out which span is selected, turn the rotary function
switch to OUTPUT mA [, short the OUTPUT SOURCE +
and jacks, and observe the 0 % output level.
To toggle and save the current output span in nonvolatile
memory (retained when the power is turned off):
1. Turn off the meter.
2. Hold down R while turning the meter on.
3. Wait at least 2 seconds until the new range shows as
0-20 or 4-20 and then release R.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fluke ProcessMeter 787B and is the answer not in the manual?

Fluke ProcessMeter 787B Specifications

General IconGeneral
Battery life140 h
Battery sizeAA
Battery technologyAlkaline
Number of batteries supported4
ManualYes
Loop voltage1000 V
Drop proof up to1 m
Operating vibration2 G
Storage temperature (T-T)-40 - 60 °C
Operating temperature (T-T)-20 - 55 °C
Operating relative humidity (H-H)0 - 95 %
Weight and Dimensions IconWeight and Dimensions
Depth50 mm
Width100 mm
Height203 mm
Weight600 g

Related product manuals