VENTILATION
IMPORTANT ::
For Republic of Ireland ventilation may be required, see IS 813, ICP3, IS 327, and any other rules
in force.
NV Models ::
No purpose provided ventilation is normally required for this appliance. The requirements of other
appliances operating in the same room or space must be taken into consideration when assessing ventilation. If
spillage is detected when commissioning the appliance then amongst other problems there may be insufficient
natural ventilation for the correct operation of the flue. This is potentially a greater problem should the property
be of modern nature. If the appliance does not spill with windows open but does with windows closed, this
proves that lack of ventilation is the problem, if not, it will be the flue at fault. Installation of an air brick is the best
solution. Any ventilation fitted must comply with BS 5871 part 2 and BS 5440 part 2.
Ventilation located underneath or within the immediate vicinity of the fire MUST NOT be used as it may adverse-
ly affect the performance of the O.D.S. system. Spillage detected during commissioning is almost always a result
of poor flue performance, which cannot be corrected by any amount of ventilation.
PLUS MModels ::
15cm
2
of purpose provided ventilation is required for this appliance, which must comply with BS
5871 part 2 and BS 5440 part 2. Ventilation located underneath or within the immediate vicinity of the fire MUST
NOT be used as it may adversely affect the performance of the O.D.S. system. If spillage is detected when com-
missioning the appliance then amongst other problems there may be insufficient natural ventilation for the cor-
rect operation of the flue. This is potentially a greater problem should the property be of modern nature. If the
appliance does not spill with windows open but does with windows closed, this proves that lack of ventilation is
the problem, if not, it will be the flue at fault. Installation of a larger air brick is the best solution.
Spillage detected during commissioning is almost always a result of poor flue performance, which cannot be cor-
rected by any amount of ventilation.
UNPACKING TTHE AAPPLIANCE
Stand the carton right way up, cut the strapping bands and remove the top end cap. Read all the instructions
before continuing to unpack or install this appliance.
Remove the packing pieces, and any bags containing other fittings or parts. When all loose parts have been
removed, the outer sleeve may be lifted off to reveal the appliance. Check that the components supplied corre-
late with the checklist given in section 7.1. Please dispose of the packaging materials at your local recycling cen-
tre.
COMPONENT CCHECKLIST
QUAANTITY DESCRIPTION
1 Firebox and burner assembly.
1 Decorative frame, one of several finishes.
10 Individual ceramic pebbles (pebble effect option only)
1 Bag of heat resistant glass crystals (glass fuel bed versions only)
1 Set of manufacturers instructions and warranty card.
1 Cable fixing kit comprising; 2 cables, 2 tensioners, 2 clamps, 4 fixing eyes, 4 fibre rawl plugs.
1 Screw pack
3 Lengths of self adhesive sealing strip.
1 Rubber grommet.
1 Allen key
5.0
6.0
4
7.0