6
© Copyright, Sunrise Tradex Corp., 2018
FIG. 2 DIMENSIONS FOR FRONT CONNECTION COIL
3.0 APPLICATIONS
3.1 VERTICAL UPFLOW
▪ Vertical upow conguration is the factory set on all models (see g. 1).
▪ If return air is to be ducted, install duct ush with oor. Use reproof gaskets of 3.2 to 6.4 mm
(⅛ to ¼ inches) thick between the ducts, unit and oor. Set unit on the oor over the opening.
IMPORTANT : Torque applied to drain connections should not exceed 15 ft-lb (see g.1 and 2).
3.2 VERTICAL DOWNFLOW
Conversion from Vertical Upow to Vertical Downow : A vertical upow unit may be
converted to vertical downow. Remove the door and indoor coil and reinstall 180° from original
position (see g. 3).
IMPORTANT : To comply with certication agencies and the National Electric Code for
horizontal right application, the circuit breaker(s) on eld-installed electric heater kits must be
re-installed following the procedure below so that the breaker switch “ON” position and marking
is up, and “OFF” position and marking is down.
▪ To rotate breaker(s): Rotate one breaker set (circuit) at a time starting with the one on the
right. Loosen both lugs on the load side of the breaker. (Make sure that wires are identied
and are reinstalled into proper breaker). Wires are bundled with wire ties, one bundle going to
the right lug and one bundle going to the left lug.
Installation Manual
14.2 mm
(1 9/16")
74.6 mm
(2 15/16")
74.6 mm
(2 15/16")
71.4 mm
(2 13/16")
7.9 mm
(5/16")
7.9 mm
(5/16")
31.8 mm
(1 1/4")
34.9 mm
(1 3/8")