Figure 3.  Flow Sensor Location  Guide
Flow Sensor Location Guide
The preferred location for mounting 
a ow sensor is on the top half of the 
pipe. The best orientation is vertical. If 
the sensor is mounted on the bottom of 
the pipe, it may be susceptible to dirt 
accumulation impacting operation. 
When mounting a sensor after the pipe 
diameter is reduced, length L must be at 
least 2 times the pipe diameter.
When mounting a sensor after a valve, 
length L must be at least 14 times the  
pipe diameter.
When mounting a sensor after an elbow, 
length L must be at least 6 times the  
pipe diameter.
When mounting a sensor before a valve or 
an elbow, length L must be at least equal 
to the pipe diameter.
Before Valve or Elbow
L > 1 X PIPE DIA.
After Elbow
L > 6 X PIPE DIA.
After Valve
L > 14 X PIPE DIA.
After Reduction
L > 2 X PIPE DIA.
Best Orientation 
is Vertical
L
L
L
L