5.3.3 Performing the emissions measurement
Preparing for the measurement
Clean boiler 2 heating days (1 heating day = 1 day during which the boiler to be
measured is in operation) before the measurement
There must be a suitable measuring port in the straight flue gas pipe for the
measurement. The measuring port must be twice the flue gas pipe diameter away
from the last upstream bend.
If the measuring port is not correctly positioned, the measuring result will be
distorted
Ensure that there is enough combustion air
Prepare adequate fuel
Ensure that there is adequate heat dissipation
Create the measurement conditions and perform the measurement
Fill the boiler approx. 1/4 full with short split wood () in accordance with the
operating instructions and heat up
Ensure that the operating conditions are fulfilled:
Return temperature min. 60 °C
Boiler temperature min. 70 °C
Chimney draught ranging from 8 - 10 Pa
Allow the fuel to burn off until a basic firebed is achieved
This will take at least one hour depending on the fuel used and the power
consumption
Open the fuel loading door, distribute the embers evenly with the furnace tool and
gauge the height of the embers
The top row of holes in the combustion chamber guards is visible
Close the fuel loading door
Once the basic firebed has been achieved (top row of holes visible in the combustion
chamber guards):
With the doors closed, press the chimney sweep button (boiler with button display)
or activate chimney sweep function in the quick menu (boiler with touchscreen)
The boiler temperature setpoint will be automatically set to 85°C for 45 minutes
All of the configured heating circuits will be activated at maximum flow
temperature for 45 minutes
Open the fuel loading door and fill the boiler with the maximum permitted amount
of fuel
If the boiler has activated reload calculation, the amount of fuel required will be
shown on the screen
Close the doors and wait approx. 10 minutes until the combustion process is
under way
Take the measurement at the designated measuring port
5
Boiler Servicing
Emissions measurement by chimney sweep or regulatory body
42 Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com

Table of Contents

Other manuals for Froling S3 Turbo

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Froling S3 Turbo and is the answer not in the manual?

Froling S3 Turbo Specifications

General IconGeneral
BrandFroling
ModelS3 Turbo
CategoryBoiler
LanguageEnglish

Related product manuals