44
Class 3 status 
codes
Class 3 includes status codes that may occur while feeding energy into the grid, but gen-
erally do not cause the process to be interrupted for any length of time. 
The inverter disconnects automatically from the grid, the grid is then monitored as specified 
and the inverter attempts to resume feeding energy into the grid.
Class 4 status 
codes
Some of the class 4 status codes necessitate intervention by a Fronius-trained service en-
gineer.
Code Description Behaviour Remedy
301 Overcurrent (AC)
Short-term interruption while 
feeding energy into the grid 
due to overcurrent in the invert-
er
 The inverter resumes with its 
startup routine.
Fault is rectified automatically; 
if this status code is displayed 
all the time: notify a Fronius-
trained service engineer.
302 Overcurrent (DC)
303
Power stage set overtempera-
ture
Short-term interruption while 
feeding energy into the grid 
due to overtemperature
 The inverter resumes with its 
startup routine.
Purge openings for cooling air 
and heat sink if necessary;
 fault is rectified automatically; 
if this status code keeps recur-
ring, contact your system engi-
neer
304 Internal temperature too high
306
LOW PV OUTPUT
 Intermediate circuit voltage 
too low for feeding energy into 
the grid
Short-term interruption while 
feeding energy into the grid
 The inverter resumes with its 
startup routine.
Fault is rectified automatically; 
if this status code occurs when 
there is sufficient insolation, 
contact your system engineer
307
LOW PV VOLTAGE
 DC input voltage too low for 
feeding energy into the grid
IMPORTANT! Due to the low level of insolation early in the morning and in the evening, the status codes 306 
(LOW PV OUTPUT) and 307 (LOW PV VOLTAGE) are displayed routinely at these times of day. These status 
codes do not indicate any kind of fault.
308 Intermediate circuit overvolt-
age
Short-term interruption while 
feeding energy into the grid
 The inverter resumes with its 
startup routine.
Fault is rectified automatically; 
if this status code is displayed 
all the time: notify a Fronius-
trained service engineer.
309 DC input voltage too high
Code Description Behaviour Remedy
401
No communication with power 
stage set possible
The inverter will automatically 
attempt to connect again and, 
if possible, will resume feeding 
energy into the grid
If the status code is displayed 
all the time: notify a Fronius-
trained service engineer
406
Power stage set temperature 
sensor faulty
407
Internal temperature sensor 
faulty
408
DC feeding into the grid detect-
ed