47
EN
Class 7 status 
codes
Class 7 status codes relate to the control system, the configuration and inverter data re-
cording, and may directly or indirectly affect the process of feeding energy into the grid.
Code Description Behaviour Remedy
668
Incorrect input signal on the 
multifunction current interface
The inverter is not feeding any 
energy into the grid. 
The status code is displayed in 
the case of an incorrect input 
signal at the multifunction cur-
rent interface and with the fol-
lowing setting:
Basic menu / Input signal / 
Mode of operation = Ext. Sig-
nal, triggering method = Ext. 
Stop
Check the devices connected 
to the multifunction current in-
terface;
if this status code keeps recur-
ring: notify a Fronius-trained 
service engineer.
Code Description Behaviour Remedy
705
Conflict when setting the in-
verter number (e.g. number al-
ready assigned)
-
Correct the inverter number via 
the Setup menu
721
EEPROM has been reinitial-
ised or EEPROM is faulty
Warning message is shown on 
the display
Acknowledge status code;
If the status code is displayed 
all the time: notify a Fronius-
trained service engineer
731
Initialisation error - USB stick is 
not supported
Warning message is shown on 
the display
Check or replace USB stick
Check the file system on the 
USB stick
If the status code is displayed 
all the time: notify a Fronius-
trained service engineer
732 Overcurrent on USB stick
733 No USB stick connected
Warning message is shown on 
the display.
Connect or check USB stick
If the status code is displayed 
all the time: notify a Fronius-
trained service engineer
734
Update file not recognised or 
not present
Warning message is shown on 
the display
Check update file (e.g. for cor-
rect file name)
If the status code is displayed 
all the time: notify a Fronius-
trained service engineer
735
Update file does not match the 
device, update file too old
Warning message appears on 
the display, update process is 
interrupted
Check update file 
and if necessary organise an 
update file to match the device 
(e.g. at http://
www.fronius.com)
If the status code is displayed 
all the time: notify a Fronius-
trained service engineer
736 Write or read error occurred
Warning message is shown on 
the display
Check USB stick and the data 
contained on it or replace USB 
stick
Never unplug a USB stick if the 
'Data Transmission' LED is still 
flashing or lit.
If the status code is displayed 
all the time: notify a Fronius-
trained service engineer