Updating inverter
software using a
USB stick
Obtain the ‘updatexx.tl’ update file
(e.g., at http://www.fronius.com, xx stands for the respective version number)
Save the update file to the highest data level of the USB stick.
Remove the screws on the data communication rack.
Pull out the data communication rack.
Insert the USB stick with the update file into the USB socket on the data communica-
tion rack.
NOTE! To ensure problem-free updates of inverter software, the USB stick
should have no hidden partitions and no encryption.
Select the ‘USB’ menu item.
Press the ‘Enter’ key.
‘Disconnect Device’ is displayed.
Use the ‘Up’ and ‘Down’ keys to se-
lect the ‘Update Software’ parameter.
Press the ‘Enter’ key.
‘wait ...’ is displayed until ...