52
Trip Limits NLMON (127 V) Trip Limits NLMON (120 V, HI1)
U
AC
[V] Clearing Time [s]
Clearing Time [cyl]
U
AC
[V] Clearing Time [s]
Clearing Time [cyl]
U < 50% 64 0.16
9 * / 8 **
60 0.16 / 0.5 ***
9 / 28 ***
50 U < 88 % 112 2
118 * / 100 **
106 2 / 21.0 ***
118 / 1258 ***
110 < U < 120 % 139 1
58 * / 50 **
132 1
58
U 120 % 152 0.16
9 * / 8 **
144 0.16
9
U
Imin
adjustable 60 - 121 0.016 - 21.0
1 - 1260 * / 1050 **
60 - 114 0.016 - 21.0
1 - 1260
U
Imax
adjustable 133 - 152 0.016 - 21.0
1 - 1260 * / 1050 **
126 - 152 0.016 - 21.0
1 - 1260
U
Omax
adjustable 133 - 152 0.016 - 4.25
1 - 255 * / 212 **
126 - 152 0.016 - 4.25
1 - 255
U
Omin
adjustable 60 - 121 0.016 - 4.25
1 - 255 * / 212 **
60 - 114 0.016 - 4.25
1 - 255
* 60 Hz
** 50 Hz
*** Setup HI1
Frequency (for all 60 Hz setups) Frequency (for all 50 Hz setups)
F [Hz] Clearing Time [s]
Clearing Time [cyl]
F [Hz] Clearing Time [s]
Clearing Time [cyl]
F
Imax
+ 0.5 > 60.5 0.16
9
> 50.5 0.16
8
F
Omax
+ 2.0 > 62.0 0.16
9
> 55.0 0.16
8
F
Imin
- 0.7 < 59.3 0.16
9
< 48.0 0.16
8
F
Omin
- 3.0 < 57.0 0.16
9
< 45.0 0.16
8
F
Imin
adjustable 50.00 -
65.00
0.016 - 600
1 - 36000
45.00 -
55.00
0.020 - 600
1 - 30000
F
Imax
adjustable 50.00 -
65.00
0.016 - 600
1 - 36000
45.00 -
55.00
0.020 - 600
1 - 30000
F
Omin
adjustable 50.00 -
65.00
0.016 - 600
1 - 36000
45.00 -
55.00
0.020 - 600
1 - 30000
F
Omax
adjustable 50.00 -
65.00
0.016 - 600
1 - 36000
45.00 -
55.00
0.020 - 600
1 - 30000

Related product manuals