EasyManua.ls Logo

Fronius Primo 10.0-1 - Field Adjustable Trip Points; Voltage Trip Point Settings

Fronius Primo 10.0-1
60 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
51
Field Adjustable Trip Points
Setup 208 V Setup 220 V
U
AC
[V] Clearing Time [s]
Clearing Time [cyl]
U
AC
[V] Clearing Time [s]
Clearing Time [cyl]
U < 50% 104 0.16
9
110 0.16
9
50 U < 88 % 183 2
118
194 2
118
110 < U < 120 % 229 1
58
242 1
58
U 120 % 249 0.16
9
264 0.16
9
U
Imin
adjustable 104 - 198 0.016 - 21.0
1 - 1260
104 - 209 0.016 - 21.0
1 - 1260
U
Imax
adjustable 218 - 288 0.016 - 21.0
1 - 1260
231 - 288 0.016 - 21.0
1 - 1260
U
Omax
adjustable 218 - 288 0.016 - 4.25
1 - 255
231 - 288 0.016 - 4.25
1 - 255
U
Omin
adjustable 104 - 198 0.016 - 4.25
1 - 255
104 - 209 0.016 - 4.25
1 - 255
Setup 240 V, Setup HI1 Setup 50HZ
U
AC
[V] Clearing Time [s]
Clearing Time [cyl]
U
AC
[V] Clearing Time [s]
Clearing Time [cyl]
U < 50% 120 0.16 / 0.5 ***
9 / 28 ***
110 0.16
8
50 U < 88 % 211 2 / 21 ***
118 / 1258 ***
194 2
100
110 < U < 120 % 264 1
58
242 1
50
U 120 % 288 0.16
9
264 0.16
8
U
Imin
adjustable 104 - 228 0.016 - 21.0
1 - 1260
104 - 209 0.016 - 21.0
1 - 1050
U
Imax
adjustable 252 - 288 0.016 - 21.0
1 - 1260
231 - 288 0.016 - 21.0
1 - 1050
U
Omax
adjustable 252 - 288 0.016 - 4.25
1 - 255
231 - 288 0.016 - 4.25
1 - 212
U
Omin
adjustable 104 - 228 0.016 - 4.25
1 - 255
104 - 209 0.016 - 4.25
1 - 212
*** Setup HI1