Maximum AC
fuse protection
Fronius 3.8–8.2
Fronius 10.0–15.0
Additional exter-
nal AC and/or DC
disconnect
Depending on the installation, an additional external AC and/or DC disconnect may be re-
quired if the inverter is installed in a location not easily accessible to utility or fire personnel.
Contact your local authorities for additional information.
AC ~
max. 63 A
24
31
max. 100 A
AC ~
24
31
Inverter Phases Max. output Max. fuse protec-
tion
Fronius Primo 3.8-1 208-240 1 / 2 3800 W 63 A
Fronius Primo 5.0-1 208-240 1 / 2 5000 W 63 A
Fronius Primo 6.0-1 208-240 1 / 2 6000 W 63 A
Fronius Primo 7.6-1 208-240 1 / 2 7600 W 63 A
Fronius Primo 8.2-1 208-240 1 / 2 8200 W 63 A
Fronius Primo 10.0-1 208-240 1 / 2 10,000 W 100 A
Fronius Primo 11.4-1 208-240 1 / 2 11,400 W 100 A
Fronius Primo 12.5-1 208-240 1 / 2 12,500 W 100 A
Fronius Primo 15.0-1 208-240 1 / 2 15,000 W 100 A
I
ΔN
100 mA
NOTE! A residual current circuit breaker for the AC connecting cable may be re-
quired depending on local regulations, the power supply company as well as oth-
er conditions. A type A residual current circuit breaker with a trip current of at least
100 mA is generally sufficient in this case. Nevertheless, false alarms can be trig-
gered for the type A residual current circuit breaker in individual cases and de-
pending on local conditions.
For this reason, Fronius recommends that you use a residual current circuit
breaker suitable for a frequency converter.