SunSpec Model Type
Depending on the SunSpec model, there are two different settings.
float: SunSpec Inverter Model 111, 112, 113 or 211, 212, 213.
int + SF: SunSpec Inverter Model 101, 102, 103 or 201, 202, 203.
Meter address
The value entered is the identification number (Unit ID) assigned to the
meter.Can be found on the user interface of the inverter in the Communic-
ation → Modbus menu.
Factory setting: 200
Meter address
The value entered is the identification number (Unit ID) assigned to the
meter.
Can be found on the user interface of the inverter in the Communication
→ Modbus menu.
Factory setting: 1
Slave as Modbus TCP
This setting is necessary to enable inverter control via Modbus. If the function
Slave as Modbus TCP is activated, the following input fields are available:
Modbus port
Number of the TCP port that is to be used for Modbus communication.
SunSpec Model Type
Depending on the SunSpec model, there are two different settings.
float: SunSpec Inverter Model 111, 112, 113 or 211, 212, 213.
int + SF: SunSpec Inverter Model 101, 102, 103 or 201, 202, 203.
Meter address
The value entered is the identification number (Unit ID) assigned to the
meter.Can be found on the user interface of the inverter in the Communic-
ation → Modbus menu.
Factory setting: 200
Inverter address
The value entered is the identification number (Unit ID) assigned to the in-
verter. Can be found on the user interface of the inverter in the Commu-
nication → Modbus menu.
Factory setting: This value is invariably defined as 1.
Inverter control via Modbus
If this option is activated, the inverter is controlled via Modbus.
Inverter control includes the following functions:
-
on/off
-
Power reduction
-
Specification of a constant power factor (cos phi)
-
Specification of a constant reactive power value
-
Battery control specifications with battery
Restrict Control
An IP address can be entered here, which is the only one authorised to
control the inverter.
123