Technical data
Fronius Symo
GEN24 12.0 SC /
12.0 Plus SC
DC input data
MPP voltage range
(at rated power)
295 – 800 V
Max. connected load (P
PV max
)
Total
PV 1
PV 2
18,000 Wp
14,000 Wp
9000 Wp
Max. processable PV power
Total
PV 1
PV 2
12,360 Wp
12,360 Wp
8600 Wp
Max. input voltage
at 1000 W/m² / -10 °C in an open cir-
cuit
1000 V
Feed-in start-up input voltage in grid
operation
5)
80 V
Max. input current
PV 1
PV 2
28.0 A
14.0 A
Max. short circuit current of module
array (I
SC PV
)
PV 1
PV 2
40 A
20 A
Max. total short circuit current of
module array
(I
SC PV1
+ I
SC PV2
= I
SC max
) 60 A
Max. inverter backfeed current to the
array
3)
PV 1
PV 2
40 A
20 A
Number of inputs - PV 1 2
Number of inputs - PV 2 1
Max. capacity of the module array to
earth
Total
PV 1
PV 2
2400 nF
1860 nF
1200 nF
Insulation resistance test limit value
between module array and earth (on
delivery)
10)
100 kΩ
Adjustable range of insulation resist-
ance test between module array and
earth
9)
10 – 10,000 k
Limit value and tripping time of the
sudden residual current monitoring
(on delivery)
30 / 300 mA / ms
60 / 150 mA / ms
90 / 40 mA / ms
169