Settings on the user interface of the Fronius Symo GEN24 SC inverter:
1
Configure the primary meter at the feed-in point in the "Device configura-
tion" → "Components" menu.
2
Configure the secondary meter in the "Device configuration" → "Compon-
ents" menu.
Settings in the system monitoring of the Fronius SnapInverter:
1
Configure the primary meter at the feed-in point in the "Settings" → "Meter"
menu.
2
Activate the limit for the entire system in the "DNO Editor" → "Dynamic
power reduction" menu. Enter the DC rated power of the entire PV system in
the "Total DC system power" input field. Enter the percentage value (50%,
60% or 70%) in the "Max. grid feed-in power" input field.
I/O power man-
agement
General
In this menu item, settings relevant for a distribution network operator (DNO) are
made. An effective power limitation in % and/or a power factor limitation can be
set.
IMPORTANT!
Select the "Technician" user for settings in this menu item, enter and the pass-
word for the "Technician" user and confirm. Settings in this menu area must only
be made by trained and qualified personnel.
"Input pattern" (assignment of individual I/Os)
1 click = white (contact open)
2 clicks = blue (contact closed)
3 clicks = grey (not used)
"Power factor (cos φ)"
"ind" = inductive
"cap" = capacitive
"DNO feedback"
When the rule is enabled, output "DNO feedback" (pin 1 recommended) must be
configured (e.g. for operating a signalling device).
For "Import" or "Export", the data format *.fpc is supported.