1
Switch off the automatic circuit break-
er and DC disconnector. Turn the DC
disconnector to the "Off" switch posi-
tion.
2
Loosen the 5 screws of the connection
area cover by rotating them 180° to
the left using a screwdriver (TX20).
Remove the connection area cover
from the device.
CAUTION!
Danger from faulty or incorrect bores.
This may lead to injuries to the eyes and hands as a result of flying debris and
sharp edges, as well as damage to the inverter.
When drilling, wear suitable protective goggles.
Only ever use a step drill when drilling.
Ensure that nothing is damaged inside the device (for example connection
block).
Adapt the diameter of the bore to match the corresponding connection.
Deburr the bores using a suitable tool.
Remove the drilling residues from the inverter.