60 %
30 %
0 %
0,95
0,90
0,85
(1)
(2)
(4)
+
-
IO 2
IO 3
I 4
I 7
I 8
I 9
IO 0
(3)
The ripple control signal receiver and the Fronius system monitoring connector are con-
nected to one another by means of a four-pin cable in accordance with the connection
diagram.
If the distance between the Fronius system monitoring datalogger and the ripple control
signal receiver exceeds 10 m, a shielded cable is recommended.
DNO Editor settings:
Appro
ved
Input pattern
Effective
power
Power factor cos
φ;
DNO output
Excluded
inverter
*
(1)
(2)
... not usable ... not considered etc. contact open etc. contact closed
"PSC editor -
AUS - Demand
Response Modes
(DRM)"
A value for the apparent power consumption and apparent power output can be entered
here for the Australia country setup.
DNO Editor –
Dynamic power
reduction
Electricity retailers or grid operators may stipulate feed-in limitations for an inverter (e.g.
max. 70% of kWp or max. 5 kW).
114