Chapter 6: Function codes and application example
34
o codes: Option functions
Code Name Data setting range Default setting
o01 Command / feedback input (Input from selection) 0, 1, 2,
10, 11, 12,
20 ,21 ,22
0
o02 Speed control (P Item) 0.01 to 200.00 10.00
o03 (I Item) 0.000 to 5.000 s 0.100
o04 (Filter time constant) 0.000 to 5000 s 0.020
o05 (Pulse line input) (Encoder pulse number) 20 to 3600 P/R 1024
o06 (Filter time constant) 0.000 to 5.000 s 0.005
o07 (Pulse compensation coefficient 1) 1 to 9999 1
o08 (Pulse compensation coefficient 2) 1 to 9999 1
o09 Feedback (Feedback input)
(Encoder pulse number)
20 to 3600 P/R
1024
o10 (Filter time constant) 0.000 to 5.000 s 0.005
o11 (Pulse compensation coefficient 1) 1 to 9999 1
o12 (Pulse compensation coefficient 2) 1 to 9999 1
o13 Speed control (Output limiter) 0.00 to 100.0 % 100.00
o14 Reserved
o15 Reserved
o16 Reserved
o17 Excessive speed deviation (Level) 0 to 50 % 10
o18 (Timer) 0.0 to 10.0 s 0.5
o19 PG abnormal error selection 0, 1, 2 2
0
o20 DIO option (DI mode selection) 0: 8 bit binary setting
1: 12 bit binary setting
4: BCD 3-digit setting 0 to 99.9
5: BCD 3-digit setting 0 to 999
0: Output frequency (before slip compensation) 0
1: Output frequency (after slip compensation)
2: Output current
3: Output voltage
4: Output torque
5: Overload rate
6: Power consumption
7: PID feedback amount
9: DC link voltage
13: Motor output
15: PID command (SV)
16: PID command (MV)
o21 (DO mode selection)
99: Individual signal output
o27 Transmission Error (Operation selection)
0 to 15 0
o28 (Timer selection) 0.0 to 60.0 s 0.0
o30 Bus setting parameter 1 0 to 255 0
o31 Bus setting parameter 2 0 to 255 0
o32 Bus setting parameter 3 0 to 255 0
o33 Bus setting parameter 4 0 to 255 0
o34 Bus setting parameter 5 0 to 255 0
o35 Bus setting parameter 6 0 to 255 0
o36 Bus setting parameter 7 0 to 255 0
o37 Bus setting parameter 8 0 to 255 0
o38 Bus setting parameter 9 0 to 255 0
o39 Bus setting parameter 10 0 to 255 0
o40 Writing function code allocation 1 0000H to FFFFH 0000H
o41 Writing function code allocation 2 0000H to FFFFH 0000H
o42 Writing function code allocation 3 0000H to FFFFH 0000H
o43 Writing function code allocation 4 0000H to FFFFH 0000H
o44 Writing function code allocation 5 0000H to FFFFH 0000H
o45 Writing function code allocation 6 0000H to FFFFH 0000H
o46 Writing function code allocation 7 0000H to FFFFH 0000H
o47 Writing function code allocation 8 0000H to FFFFH 0000H
o48 Read function code allocation 1 0000H to FFFFH 0000H
o49 Read function code allocation 2 0000H to FFFFH 0000H
o50 Read function code allocation 3 0000H to FFFFH 0000H
o51 Read function code allocation 4 0000H to FFFFH 0000H
o52 Read function code allocation 5 0000H to FFFFH 0000H
o53 Read function code allocation 6 0000H to FFFFH 0000H
o54 Read function code allocation 7 0000H to FFFFH 0000H
o55 Read function code allocation 8 0000H to FFFFH 0000H
o56 Read function code allocation 9 0000H to FFFFH 0000H
o57 Read function code allocation 10 0000H to FFFFH 0000H
o58 Read function code allocation 11 0000H to FFFFH 0000H
o59 Read function code allocation 12 0000H to FFFFH 0000H