Chapter 8: Specifications
_______________________________________________________________________________________________________________
39
8. SPECIFICATION AND EXTERNAL DIMENSIONS
8.1 Specifications
8.1.1 Three-phase 200 V class series
*1 Fuji 4-pole standard motor
*2 Rated capacity is calculated assuming the output rated voltage as 220 V.
*3 Output voltage cannot exceed the power supply voltage.
*4 Ta= 40° C, Fc= 15 kHz, ED= 100%.
*5 The value is calculated assuming that the inverter is connected with a power supply with the capacity
of 500 kVA (or 10 times the inverter capacity if the inverter capacity exceeds 50 kVA) and %X is 5%.
*6 Obtained when a DC reactor (DCR) is used.
*7 Average braking torque obtained when reducing the speed from 60 Hz with AVR control OFF. (It
varies with the efficiency of the motor.)
*8 Average braking torque obtained by use of an external braking resistor (standard type available as
option)
*9
3)-61800 (IEC 67×
(V) voltageaverage phase-Three
(V) eMin voltag - (V) eMax voltag
(%) unbalance Voltage =
If this value is 2 to 3%, use an optional AC reactor (ACR).
Note: A box () in the above table replaces A, C, J, or K depending on the shipping destination.