Chapter 9: Options
_______________________________________________________________________________________________________________
48
9. OPTIONS
9.1 Options table
Option name Function and application
DC reactor (DCRE)
The DC reactor is used to reduce harmonic components on the input current (mains supply) of the
inverter.
Note: DO NOT FORGET to remove the DC link bar between P1 and P(+) before installing this option.
Output filter(OFLE)
Install an output filter between the inverter and the motor to:
1) Suppress the voltage fluctuation at the motor input terminals.
2) Reduce leakage current from the motor power cable (motor supply), due to harmonic components.
3) Reduce emission and induction noise generated from the motor power cable.
Note: When using an OFLE, set the switching frequency of the inverter (function code F26) within the
allowable range specified by the filter manufacturer, otherwise the filter will overheat.
Ferrite ring reactors
(ACL)
The ferrite ring reactors are used to reduce radiated emissions from the inverter.
EMC input filter The EMC input filter is used to make the inverter to conform to European EMC directives.
Main options
AC reactor
(ACRE)
The AC reactor is connected to the inverter input (mains supply) when the inter-phase voltage
unbalance of the AC mains is between 2% and 3%.
67
(V)voltage average phase 3
(V)voltage Min.(V)voltage Max.
=unbalance voltage phase-Inter ×
Multi-function keypad
(TP-G1)
A
llows the user to monitor the status of the inverter
(
volta
g
e, output current, input power,…
)
, as well as
to set parameters values in a conversational mode (6 languages available). It is able to store three
complete inverter function sets. It includes a Liquid Crystal Display.
Extension cable for
keypad (CB-..S)
The extension cable allows to connect the keypad to the inverter remotely.
Three lengths are available: 5 m (CB-5S), 3 m (CB-3S) y 1 m (CB-1S).
RS485 Communications
card (OPC-E1-RS)
This card adds an additional communications port to the inverter that allows to connect a PLC or PC.
PG option card
(OPC-E1-PG)
This card allows to connect a pulse train signal or a signal from a Pulse Generator. This signal may be
used to generate a speed reference or to close the speed and/or position loop. The level of the signal
that can be connected to this card is 5 V TTL.
PG3 option card
(OPC-E1-PG3)
This card allows to connect a pulse train signal or a signal from a Pulse Generator. This signal may be
used to generate a speed reference or to close the speed and/or position loop. The level of the signal
that can be connected to this card is 12~15 V HTL.
DeviceNet interface
card (OPC-E1-DEV)
This card is used to communicate the inverter to a DeviceNet master unit.
ProfiBus DP interface
card (OPC-E1-PDP)
This card is used to communicate the inverter to a ProfiBus DP master unit.
CC Link interface card
(OPC-E1-CCL)
This card is used to communicate the inverter to a device with CC Link interface.
Additional input-output
card (OPC-E1-DIO)
This card is allows to set the frequency reference in Binary or BCD code. Also enables monitoring by
using binary code.
Loader software
PC software, Windows GUI (Graphics user interface) based that allows to set inverter function values
more easily. Also allows to upload/download all the function values to/from a file.
Operation and communication options
Attachment for external
cooling (PB-F1)
With this adapter you can install the inverter in the panel in such a way that the heatsink is outside of
the cabinet.