Conformity to the Low Voltage Directive in the EU (Continued)
13. To prevent the risk of hazardous accidents that could be caused by damage of the inverter,
install the specified fuses in the supply side (primary side) according to the following tables.
- Breaking capacity: Min. 10 kA
- Rated voltage: Min. 500 V
Power
supply
voltage
Nominal
applied
motor (HP)
Inverter type
Fuse rating
(A)
7.5
FRN0025C2S-2U
125(IEC60269-4)
10
FRN0033C2S-2U
160(IEC60269-4)
15
FRN0047C2S-2U
160(IEC60269-4)
Three-phase
200V
20
FRN0060C2S-2U
200(IEC60269-4)
7.5
FRN0013C2S-4U
80(IEC60269-4)
10
FRN0018C2S-4U
80(IEC60269-4)
15
FRN0024C2S-4U
125(IEC60269-4)
Three-phase
400V
20
FRN0030C2S-4U
160(IEC60269-4)
14. Use this inverter at the following power supply system.