EasyManua.ls Logo

Fujitsu AB*A30LBT - Electric Characteristics

Fujitsu AB*A30LBT
100 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
08-04
8-3. ELECTRIC CHARACTERISTICS
Model Name
AB*A30LBT AB*A36LBT
Voltage V
Frequency Hz
Max Operating Current A 17.0 20.0
Circuit breaker A 0.6 0.9
Connection Cable
mm
2
1.5 - 2.5 1.5 - 2.5
Limited wiring length m 26 31
*1)Wiring Spec.
Power Supply
230
50
Main fuse (Circuit breaker)
current
A
Power cable
mm
2
*2)Limited wiring length m 21 18
*1) Wiring spec.
Selected sample
(Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
*2) Limited wiring length :
This is the wiring length in case voltage descent is less than 2%.
When the wiring length becomes long, please select the wiring of a more larger diameter.
15.0
*1) Wiring spec.
230
50
4.0
Model Name
AO*A30LBTL AO*36LBTL
Power Supply
Starting current
Max Operating Current
Voltage
Frequency
V
Hz
A
A
20
25
20

Table of Contents