Connecting the pipes
CAUTION
• Seal the pipe route hole with putty (locally purchased) such that there are no gaps. Small in-
sects or animals that are trapped in the outdoor unit may cause a short circuit in the electrical
component box.
• After completing all the pipe connection by brazing, perform the indoor unit pipe connection with
a flare joint.
• When removing the pinch pipe or brazing the joint pipe, carry out the work while cooling down
the 3-way valve sufficiently.
• Braze the joint pipe onto the 3-way valves at the liquid and gas side. Install the joint pipe appropri-
ately so that it can be connected easily with the main pipe.
• Braze the joint pipe at the liquid and gas side with the main pipe.
• Be sure to supply nitrogen when brazing.
Connection example (For Gas pipe φ 22.22)
noitcennoc mottoBnoitcennoc tnorF
Liquid pipe
Gas pipe
Joint pipe A
(accessory)
Liquid pipe
(locally purchased)
Gas pipe
(locally purchased)
Joint pipe B
(accessory)
(locally purchased)
(locally purchased)
- 200 -
3-3. Pipe connection 3. Pipe installation
SYSTEM
DESIGN
SYSTEM
DESIGN

Table of Contents

Other manuals for Fujitsu AO G24LBCB Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AO G24LBCB Series and is the answer not in the manual?

Fujitsu AO G24LBCB Series Specifications

General IconGeneral
BrandFujitsu
ModelAO G24LBCB Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals