EasyManua.ls Logo

Fujitsu AOU12RLFC

Fujitsu AOU12RLFC
151 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7. Additional charge calculation
7-1. Model: AOU12RLFC
Refrigerant type R410A
Refrigerant amount
lb oz 2 lb 10 oz
g 1,200
¢ Refrigerant charge
Total pipe length
ft 49 or less 66 (Max.)
0.22 oz/ft
(20 g/m)
m 15 or less 20 (Max.)
Additional charge
oz 0 3.5
g 0 100
7-2. Model: AOU18RGLX
Refrigerant type R410A
Refrigerant amount
lb oz 4 lb 10.1 oz
g 2,100
¢ Refrigerant charge
Total pipe length
ft 66 or less 98 131 164 (Max.)
0.22 oz/ft
(20 g/m)
m 20 or less 30 40 50 (Max.)
Additional charge
oz 0 7.1 14.1 21.2
g 0 200 400 600
7-3. Models: AOU24RGLX, AOU30RGLX, and AOU36RGLX
Refrigerant type R410A
Refrigerant amount
lb oz 4 lb 10.1 oz
g 2,100
¢ Refrigerant charge
Total pipe length
ft 66 or less 98 131 164 (Max.)
0.43 oz/ft
(40 g/m)
m 20 or less 30 40 50 (Max.)
Additional charge
oz 0 14.1 28.2 42.3
g 0 400 800 1,200
- 123 -
7-1. Model: AOU12RLFC 7. Additional charge calculation
OUTDOOR UNIT
AOU12-48R
OUTDOOR UNIT
AOU12-48R