7. Safety devices
Type of protection Protection form
Model
ARU12RGLX
ARU18RGLX
ARU24RGLX
Circuit protection Current fuse (PCB*) 250 V, 5 A
Fan motor protection
Thermal protection
program
Activate
239±59 °F (115±15 °C)
Fan motor stop
Reset
158 °F (70 °C)
Fan motor restart
Current protection Activate 1.64 A 2.13 A
Type of protection Protection form
Model
ARU30RGLX
ARU36RGLX
ARU42RGLX
ARU48RGLX
Circuit protection Current fuse (PCB*) 250 V, 10 A
Fan motor protection
Thermal protection
program
Activate
212±41 °F (100±5 °C)
Fan motor stop
Reset
158±59 °F (70±15 °C)
Fan motor restart
Current protection Activate 7.58 A 8.89 A