¢ Model: ARU48RGLX
AFR CFM 1,501
Indoor temperature
°FDB 60 65 70 72 75
Outdoor temperature
°FDB °FWB
TC IP TC IP TC IP TC IP TC IP
kBtu/h kW kBtu/h kW kBtu/h kW kBtu/h kW kBtu/h kW
-5 -7 35.10 4.57 34.25 4.66 33.43 4.76 32.58 4.85 31.76 4.95
5 3 37.89 4.57 36.97 4.66 36.09 4.76 35.17 4.85 34.28 4.95
14 12 42.84 4.57 41.83 4.66 40.82 4.76 39.78 4.86 38.78 4.95
17 21 44.68 4.57 43.63 4.66 42.58 4.76 41.50 4.86 40.44 4.95
23 19 48.22 4.57 47.06 4.66 45.90 4.76 44.77 4.85 43.60 4.95
32 28 51.85 4.57 50.63 4.66 49.41 4.76 48.16 4.86 46.93 4.95
41 37 55.98 4.58 54.63 4.67 53.29 4.77 51.98 4.87 50.63 4.97
47 43 57.75 4.58 56.38 4.68 55.00 4.77 53.63 4.87 52.25 4.97
50 47 59.22 4.57 57.81 4.66 56.41 4.75 54.97 4.85 53.57 4.95
59 50 60.62 4.53 59.16 4.62 57.72 4.71 56.28 4.81 54.85 4.88
AFR
m
3
/h
2,550
Indoor temperature
°CDB 15.6 18.3 21.1 22.2 23.9
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-20.6 -21.7 10.29 4.57 10.04 4.66 9.80 4.76 9.55 4.85 9.31 4.95
-15 -16.1 11.10 4.57 10.84 4.66 10.58 4.76 10.31 4.85 10.05 4.95
-10 -11.1 12.56 4.57 12.26 4.66 11.96 4.76 11.66 4.86 11.36 4.95
-8.3 -6.1 13.10 4.57 12.79 4.66 12.48 4.76 12.16 4.86 11.85 4.95
-5 -7.2 14.13 4.57 13.79 4.66 13.45 4.76 13.12 4.85 12.78 4.95
0 -2.2 15.20 4.57 14.84 4.66 14.48 4.76 14.11 4.86 13.76 4.95
5 2.8 16.41 4.58 16.01 4.67 15.62 4.77 15.23 4.87 14.84 4.97
8.3 6.1 16.93 4.58 16.52 4.68 16.12 4.77 15.72 4.87 15.31 4.97
10 8.3 17.36 4.57 16.94 4.66 16.53 4.75 16.11 4.85 15.70 4.95
15 10 17.77 4.53 17.34 4.62 16.92 4.71 16.50 4.81 16.08 4.88
- 25 -
4-2. Heating capacity 4. Capacity table
DUCT TYPE
ARU12-48RGLX
DUCT TYPE
ARU12-48RGLX