13) Control switching of external heaters
Sets the control method for external heater to be used.
For details, refer to Chapter 8-4. "Details of function" on page 58
Function
number
Setting value Setting description
Factory
setting
61
00 Auxiliary heater control 1
01 Auxiliary heater control 2
02 Heat pump prohibition control
03 Auxiliary heater control by outdoor temperature 1
04 Auxiliary heater control by outdoor temperature 2
05 Auxiliary heater control by outdoor temperature 3
06 Auxiliary heat pump control
07 Auxiliary heat pump control by outdoor temperature 1
08 Auxiliary heat pump control by outdoor temperature 2
09 Auxiliary heat pump control by outdoor temperature 3
14) Operating temperature switching of external heaters
Sets the temperature conditions when the external heater is ON.
For details, refer to Chapter 8-4. "Details of function" on page 58.
Function
number
Setting
value
Setting description
Factory
setting
Setting value of function 61:
00 01 to 09
Heater: On Heater: Off Heater: On Heater: Off
62
00 -5.4 °F (-3 °C) -1.8 °F (-1 °C) -0.9 °F (-0.5 °C) 0.9 °F (0.5 °C)
01 -3.6 °F (-2 °C) -1.8 °F (-1 °C) -1.8 °F (-1 °C) 0.9 °F (0.5 °C)
02 -3.6 °F (-2 °C) -1.8 °F (-1 °C) -3.6 °F (-2 °C) 0.9 °F (0.5 °C)
03 -5.4 °F (-3 °C) -1.8 °F (-1 °C) -5.4 °F (-3 °C) 0.9 °F (0.5 °C)
04 -7.2 °F (-4 °C) -1.8 °F (-1 °C) -7.2 °F (-4 °C) 0.9 °F (0.5 °C)
05 -9.0 °F (-5 °C) -1.8 °F (-1 °C) -9.0 °F (-5 °C) 0.9 °F (0.5 °C)
06 -5.4 °F (-3 °C) -0.9 °F (-0.5 °C) -0.9 °F (-0.5 °C) 0 °F (0 °C)
07 -3.6 °F (-2 °C) -0.9 °F (-0.5 °C) -1.8 °F (-1 °C) 0 °F (0 °C)
08 -3.6 °F (-2 °C) -0.9 °F (-0.5 °C) -3.6 °F (-2 °C) 0 °F (0 °C)
09 -5.4 °F (-3 °C) -0.9 °F (-0.5 °C) -5.4 °F (-3 °C) 0 °F (0 °C)
10 -7.2 °F (-4 °C) -0.9 °F (-0.5 °C) -7.2 °F (-4 °C) 0 °F (0 °C)
11 -9.0 °F (-5 °C) -0.9 °F (-0.5 °C) -9.0 °F (-5 °C) 0 °F (0 °C)
12 -5.4 °F (-3 °C) 0 °F (0 °C) -0.9 °F (-0.5 °C) -0.9 °F (-0.5 °C)
13 -3.6 °F (-2 °C) 0 °F (0 °C) -1.8 °F (-1 °C) -0.9 °F (-0.5 °C)
14 -3.6 °F (-2 °C) 0 °F (0 °C) -3.6 °F (-2 °C) -0.9 °F (-0.5 °C)
15 -5.4 °F (-3 °C) 0 °F (0 °C) -5.4 °F (-3 °C) -0.9 °F (-0.5 °C)
16 -7.2 °F (-4 °C) 0 °F (0 °C) -7.2 °F (-4 °C) -0.9 °F (-0.5 °C)
17 -9.0 °F (-5 °C) 0 °F (0 °C) -9.0 °F (-5 °C) -0.9 °F (-0.5 °C)
- 90 -
9-2. Function settings by using remote controller 9. Function settings
DUCT TYPE
ARU12-48RGLX
DUCT TYPE
ARU12-48RGLX

Table of Contents

Other manuals for Fujitsu AOU12RLFC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOU12RLFC and is the answer not in the manual?

Fujitsu AOU12RLFC Specifications

General IconGeneral
BrandFujitsu
ModelAOU12RLFC
CategoryAir Conditioner
LanguageEnglish

Related product manuals