4-2. Heating capacity
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
¢ ARXG45KHTA
AFR
m
3
/h
3,350
Indoor temperature
°CDB 16 18 20 22 24
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-15 -16 12.04 4.43 11.75 4.45 11.46 4.48 11.19 4.48 10.53 4.48
-10 -11 13.37 4.62 13.05 4.64 12.73 4.67 12.43 4.67 11.69 4.67
-5 -7 14.70 4.81 14.35 4.83 14.00 4.86 13.67 4.86 12.86 4.86
0 -2 15.48 4.99 15.11 5.02 14.74 5.05 14.40 5.05 13.54 5.05
5 3 16.57 4.84 16.18 4.86 15.78 4.89 15.42 4.89 14.50 4.89
7 6 17.01 4.83 16.61 4.85 16.20 4.88 15.82 4.88 14.88 4.88
10 8 17.72 4.82 17.29 4.84 16.87 4.87 16.48 4.87 15.50 4.87
15 10 18.89 4.80 18.44 4.83 17.99 4.85 17.57 4.85 16.53 4.85
20 15 20.07 4.78 19.59 4.81 19.11 4.83 18.66 4.83 17.55 4.83
24 18 21.01 4.77 20.50 4.80 20.00 4.82 19.54 4.82 18.38 4.82
¢ ARXG54KHTA
AFR
m
3
/h
3,350
Indoor temperature
°CDB 16 18 20 22 24
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-15 -16 12.95 5.16 12.65 5.19 12.34 5.22 12.05 5.22 11.33 5.22
-10 -11 14.39 5.38 14.04 5.41 13.70 5.44 13.38 5.44 12.59 5.44
-5 -7 15.82 5.60 15.44 5.63 15.07 5.66 14.72 5.66 13.84 5.66
0 -2 17.20 5.82 16.79 5.85 16.38 5.88 16.00 5.88 15.05 5.88
5 3 18.42 5.20 17.98 5.23 17.54 5.26 17.13 5.26 16.11 5.26
7 6 18.90 5.20 18.45 5.22 18.00 5.25 17.58 5.25 16.54 5.25
10 8 19.69 5.18 19.22 5.21 18.75 5.24 18.31 5.24 17.22 5.24
15 10 20.99 5.17 20.49 5.19 19.99 5.22 19.52 5.22 18.36 5.22
20 15 22.30 5.15 21.76 5.17 21.23 5.20 20.74 5.20 19.50 5.20
24 18 23.34 5.13 22.78 5.16 22.23 5.19 21.71 5.19 20.42 5.19
- 8 -
4-2. Heating capacity 4. Capacity table
DUCT TYPE
ARXG45, 54KHTA
DUCT TYPE
ARXG45, 54KHTA