7. Additional charge calculation
7-1. Models: AOYG45KRTA and AOYG54KRTA
Refrigerant type R32
Refrigerant amount g 2,700
¢ Refrigerant charge
Total pipe length m 30 or less 40 50 (Max.)
40 g/m
Additional charge amount g 0 400 800
- 42 -
7-1. Models: AOYG45KRTA and AOYG54KRTA 7. Additional charge calculation
OUTDOOR UNIT
AOYG45, 54KRTA
OUTDOOR UNIT
AOYG45, 54KRTA