EasyManuals Logo

Fujitsu ARXG54KHTA Design & Technical Manual

Fujitsu ARXG54KHTA
61 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #6 background imageLoading...
Page #6 background image
1. Specifications
Type
Duct
Inverter heat pump
Model name ARXG45KHTA ARXG54KHTA
Power supply 3N 400 V ~ 50 Hz
Power supply intake Outdoor unit
Available voltage range 342—457 V
Capacity
Cooling
Rated
kW 12.1 13.4
Btu/h 41,300 45,700
Min.—Max.
kW 4.0—14.0 5.0—14.5
Btu/h 13,600—47,800 17,100—49,400
Heating
Rated
kW 13.5 15.5
Btu/h 46,100 52,900
Min.—Max.
kW 5.0—16.2 5.5—18.0
Btu/h 17,100—55,300 18,800—61,400
Input power
Cooling
Rated
kW
4.16 4.77
Max. 5.22 5.59
Heating
Rated 3.61 4.18
Max. 5.07 5.67
Current
Cooling Rated
A
7.6 8.5
Heating Rated 6.8 7.6
Power factor
Cooling
%
79.4 81.7
Heating 77.4 79.5
EER Cooling
kW/kW
2.91 2.81
COP Heating 3.74 3.71
Moisture removal L/h (pints/h) 1.5 (2.6) 2.0 (3.5)
Maximum operating current*
1
Cooling
A
14
Heating 14
Fan
Airflow rate
Cooling
HIGH
m
3
/h
3,350
MED 2,850
LOW 2,430
Heating
HIGH 3,350
MED 2,850
LOW 2,430
Type × Q'ty Sirocco fan × 2
Motor output W 490
Static pressure range Pa 100 to 250
Sound pressure level*
2
Cooling
HIGH
dB (A)
47
MED 43
LOW 40
Heating
HIGH 47
MED 43
LOW 40
Heat exchanger type
Dimensions (H × W × D)
mm
336 × 890 × 53.2
Fin pitch 1.3
Rows × Stages 4 × 16
Pipe type Copper
Fin type Aluminum
Enclosure
Material Steel sheet
Color
Dimensions
(H × W × D)
Net
mm
400 × 1,050 × 500
Gross 460 × 1,230 × 640
Weight
Net
kg
46
Gross 51
Connection pipe
Size
Liquid
mm (in)
Ø9.52 (3/8)
Gas Ø15.88 (5/8)
Method Flare
Operation range
Cooling
°C 18 to 32
%RH 80 or less
Heating °C 16 to 30
Drain port
Material PVC
Tip diameter mm Ø26.0 (I.D.), Ø32.0 (O.D.)
Drain hose
Material PVC
Tip diameter mm Ø25.0 (I.D.), Ø32.0 (O.D.)
Remote control (Option)
Wired remote controller, Wireless remote controller, Mobile app*
3
(FGLair
)
NOTES:
Specifications are based on the following conditions:
Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length: 5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
Standard static pressure: 100 Pa
Protective function might work when using it outside the operation range.
*
1
: Maximum operating current is the total current of the indoor unit and the outdoor unit.
*
2
: Sound pressure level:
Measured values in manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
*
3
: Available on Google Play
store or on App Store
®
. Optional WLAN adapter is also required. For details, refer to the setting manual.
This data is based on EN 14511 standard.
- 2 -
1. Specifications
DUCT TYPE
ARXG45, 54KHTA
DUCT TYPE
ARXG45, 54KHTA

Table of Contents

Other manuals for Fujitsu ARXG54KHTA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARXG54KHTA and is the answer not in the manual?

Fujitsu ARXG54KHTA Specifications

General IconGeneral
BrandFujitsu
ModelARXG54KHTA
CategoryAir Conditioner
LanguageEnglish

Related product manuals