02 - 23
)
-
OUTDOOR UNIT
AOTG09-22LV
OUTDOOR UNIT
AOTG09-22LV
ELECTRIC CHARACTERISTICS9.
Model name AOTG09LV AOTG12LV AOTG18LV AOTG22LV
Power supply
Voltage V 240 ~
Frequency Hz 50
*1) Max operating current A 7.5 9.0 13.5 17.5
Starting Current A 3.5 5.0 6.5 8.5
*2) Wiring spec.
Main Fuse (Circuit
breaker) Current
A10 16 20
Power Cable mm
2
1.5 2.5 4.0
*3) Limited wiring length m 21 17 19 24
Use conformed cable with Type245 IEC57.
*1) The maximum current is the total current of indoor unit and outdoor unit.
*2)Wiring spec. :
Selected Sample
(Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
*3) Limited wiring length :
This is the wiring length in case voltage descent is less than 2%.
When the wiring length becomes long, please select the wiring of a more larger diameter.