2-9. E: 32. Indoor unit main PCB error (Indoor unit)
Indicator
Indoor unit
Operation indicator 3 time flash
Timer indicator 2 time flash
Economy indicator Continuous flash
Error code E: 32
outdoor unit
Refer to “Error code table (Outdoor unit: for 34 model
only)” on page 1
Detective actuator Indoor unit main PCB
When power is on and there is some below case.
1.
When model information of EEPROM is incorrect.
2. When the access to EEPROM failed.
Forecast of cause
External cause
Defective connection of electric components
Controller PCB failure
Check point 1. Reset power supply and operate
If no, go to "Check point 1-2".
Does error indication show again?
↓
Check point 2. Check Indoor unit electric compo-
nents
• Check all connectors. (loose connector or
incorrect wiring)
•
Check any shortage or corrosion on PCB.
↓
Check point 3. Replace main PCB
Change controller PCB.
↓
End
Check point 1-2. Check external cause such as
noise
• Check if the ground connection is proper.
• Check if there is any equipment that causes
harmonic wave near the power cable (Neon
light bulb or any electronic equipment which
causes harmonic wave).
↓
End
NOTE: EEPROM
EEPROM (Electronically Erasable and Programmable Read Only Memory) is a non-volatile
memory which keeps memorized information even if the power is turned off. It can change
the contents electronically. To change the contents, it uses higher voltage than normal, and
it cannot change a partial contents. (Rewriting shall be done upon erasing the all contents.)
There is a limit in a number of rewriting.
2-9. E: 32. Indoor unit main PCB error (Indoor unit) - (03-22) - 2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING