- 30 -
WALL MOUNTED
ASU30RLE
NOTE: Input of Operation/Stop depends on the setting of function setting 46.
00: Operation/Stop mode 1 (R.C. enabled)
01: (Setting prohibited)
02: Forced stop
03: Operation/Stop mode 2 (R.C. disabled)
Input signal type
Indoor unit
Input signal type is only "Edge".
External input and output PCB
The input signal type can be selected.
Signal type (edge or pulse) can be switched by the DIP switch SW302 on the External input and
output PCB.
860-08A
Cooling
thermostat On
Heating
thermostat On
Remote
controller output
External heater
output
9 60-09 B Error status Operation/Stop
Indoor unit fan
operation status
External heater
output
10 60-10 C
Indoor unit fan
operation status
Operation/Stop Error status
External heater
output
11 60-11 D
External heater
output
Operation/Stop
Indoor unit fan
operation status
Error status
12 60-12 D
Set point
attainment
status
Operation/Stop
Indoor unit fan
operation status
Error status
Mode
Function
setting
Rotary
SW
External output
Indoor unit External input and output PCB
CN3
1
CN310
2
CN311
3
CN312
Edge
Edge
Pulse
The width of pulse must be longer than 200 msec.