- 72 -
OUTDOOR UNIT
AOU30RLXEH
10. Electrical characteristics
*1: Minimum Circuit Ampacity (Calculation based on UL1995)
*2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate
devices complied to the regional standard.
*3: Maximum Circuit Breaker
*4: Limit voltage drop to less than 2%. If voltage drop is 2% or more, increase cable conductor size.
Model name ASU30RLE
Power supply Voltage V 208/230
Frequency Hz 60
MCA *1 A 25.6
Starting current A 18.7
Wiring spec. *2
MAX. CKT. BKR *3 A 30
Power cable AWG 10
Connection cable *4 AWG 14
Limited wiring length ft (m) 249 (76)