EasyManua.ls Logo

Fujitsu ASU30RLE - Safety Devices

Fujitsu ASU30RLE
89 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- 73 -
OUTDOOR UNIT
AOU30RLXEH
11. Safety devices
Type of
protection
Protection form
Model
AOU30RLXEH
Circuit protection
Current fuse (Near the terminal) 250 V, 25 A
Current fuse (Filter PCB)
250 V, 10 A
250 V, 5 A
Current fuse (Main PCB) 250 V, 3.15 A
Current fuse (Out of PCB) 250 V, 5 A
Fan motor
protection
Thermistor protection
Activate
122±9 °C
Fan motor stop
Reset
116
+10
-9
°C
Fan motor restart
Compressor
protection
Terminal protection
program
(Compressor temp.)
Activate
108 °C
Compressor stop
Reset
After 40 minutes
Compressor restart
Thermal protection
program
(Discharge temp.)
Activate
110°C
Compressor stop
Reset
After 7 minutes
Compressor restart
High pressure
protection
Pressure switch
Activate
4.2±0.1 MPa
Compressor stop
Reset
3.2±0.15 MPa
Compressor restart
High pressure
protection
Pressure switch
Activate
4.2±0.1 MPa
Compressor stop
Reset
3.2±0.15 MPa
Compressor restart
Low pressure
protection
Pressure sensor
Activate
4.2±0.1 MPa
Compressor stop
Reset
3.2±0.15 MPa
Compressor restart

Other manuals for Fujitsu ASU30RLE