- 36 -
WALL MOUNTED
ASU30RLE
Control output function
Operation/Stop status
The output is low when the unit is stopped.
Error status
The output is ON when an error is generated for the indoor unit.
Mode
Function
setting /
Rotary SW on
External input and
output PCB
External output
Output
signal
Command
0-1
0-2
60-00 / 1, 2 Output of indoor unit CN3
Low High Operation
High Low Stop
0-1 60-00 / 1
External input and
output PCB
CN310
Off On Operation
On Off Stop
Mode
Function
setting /
Rotary SW on
External input and
output PCB
External output
Output
signal
Command
9 60-09 / B Output of indoor unit CN3
Low High Error
High Low Normal
0-1 60-00 / 1
External input and
output PCB
CN311
Off On Error
On Off Normal
Operation
Stop
High
Low
CN3
On
Off
CN310
Indoor unit
Error
Normal
High
Low
CN3
On
Off
CN310―312
Indoor unit