Forced thermostat off function
Function
setting /
Rotary SW of External
input and output PCB
External input Input signal Command
60-00 / 2
External input and output
PCB
Input 1
Off → On Thermostat off
60-02 / 4
60-05 / 7
60-06 / 8
60-08 / A
60-09 / B
60-10 / C
On → Off
Normal
operation
60-11 / D
On
Off
On
Off
Compressor
Room temp.
Set temp.
Input
¢
Control output function
Function
setting /
Rotary SW of External
input and output PCB
External output Output signal Command
60-00 / 1, 2
60-06 / 8
Output of indoor unit CN47
Low → High Operation
High → Low Stop
60-00 / 1
External input and output
PCB
Output 1
Off → On Operation
60-09 / B
60-10 / C
On → Off Stop
60-11 / D
The output is low when the unit is stopped.
Operation
Stop
High
Low
CN47
On
Off
Output 1
Indoor unit
- 95 -
11-4. Details of function 11. External input and output (Compact cassette type and slim duct type indoor unit)
MULTI-SPLIT TYPE
5-unit type
MULTI-SPLIT TYPE
5-unit type

Table of Contents

Other manuals for Fujitsu ASUH07LPAS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASUH07LPAS and is the answer not in the manual?

Fujitsu ASUH07LPAS Specifications

General IconGeneral
BrandFujitsu
ModelASUH07LPAS
CategoryAir Conditioner
LanguageEnglish

Related product manuals