2-2. Slim duct type
Model name ADUH07LUAS1 ADUH09LUAS1 ADUH12LUAS1
Power supply 208/230 V ~ 60 Hz
Available voltage range 187—264 V
Capacity Btu/h class 7,000 9,000 12,000
Input power W 33 49 58
Running current A 0.30 0.35
Fan
Airflow rate
Cooling
HIGH
CFM (m
3
/h)
324 (550) 353 (600) 382 (650)
MED 288 (490) 324 (550) 353 (600)
LOW 277 (470) 294 (500) 324 (550)
QUIET 259 (440) 265 (450) 283 (480)
Heating
HIGH 324 (550) 353 (600) 382 (650)
MED 288 (490) 324 (550) 353 (600)
LOW 277 (470) 294 (500) 324 (550)
QUIET 259 (440) 265 (450) 283 (480)
Type × Qty Sirocco × 2
Motor output W 80 81
Recommended static pressure inWG (Pa) 0 to 0.36 (0 to 90)
Sound pressure level*
1
Cooling
HIGH
dB (A)
28 29
MED 26 27 28
LOW 25 26 27
QUIET 24 25 26
Heating
HIGH 28 29
MED 26 28
LOW 25 27
QUIET 24
Heat exchanger type
Dimensions (H × W × D) in (mm) 11-9/16 × 19-11/16 × 1-9/16 (294 × 500 × 39.9)
Fin pitch FPI 20
Rows × Stages 2 × 14 3 × 14
Pipe type Copper tube
Fin type Aluminum
Enclosure
Material Steel sheet
Color —
Dimensions
(H × W × D)
Net
in (mm)
7-13/16 × 27-9/16 × 24-7/16 (198 × 700 × 620)
Gross 10-13/16 × 37-3/16 × 30-3/8 (274 × 945 × 772)
Weight
Net
lb (kg)
35 (16) 37 (17)
Gross 46 (21) 49 (22)
Connection pipe
Size
Liquid
in (mm)
Ø1/4 (Ø6.35)
Gas Ø3/8 (Ø9.52)
Method Flare
Operation range
Cooling
°F (°C) 64 to 90 (18 to 32)
%RH 80 or less
Heating °F (°C) 60 to 86 (16 to 30)
Remote controller (Option)
Wired, Mobile app*
2
[FGLairâ„¢]
Drain hose
Material HARD PVC
Tip diameter in (mm) Ø1 (Ø25) (I.D.), Ø1-1/4 (Ø32) (O.D.)
NOTES:
• The protective function might work when using it outside the operation range.
• *
1
: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• *
2
: Available on Google Play
â„¢
store or on App Store
®
. Optional WLAN adapter is also required. For details, refer to the setting manual.
- 7 -
2-2. Slim duct type 2. Specifications
MULTI-SPLIT TYPE
5-unit type
MULTI-SPLIT TYPE
5-unit type

Table of Contents

Other manuals for Fujitsu ASUH07LPAS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASUH07LPAS and is the answer not in the manual?

Fujitsu ASUH07LPAS Specifications

General IconGeneral
BrandFujitsu
ModelASUH07LPAS
CategoryAir Conditioner
LanguageEnglish

Related product manuals