10. Safety devices
Indoor unit
type
Model name PCB* fuse
Fan motor thermal
protector
Terminal thermal
fuse
Float
switch
Compact
cassette
ACUH07LUAS1
ACUH09LUAS1
ACUH12LUAS1
ACUH18LUAS1
250 V, 5 A
Activate: 212 ±27°F
(100 ±15°C)
Fan motor stop
Reset: 203 ±18°F
(95 ±10°C)
Fan motor restart
― ○
Slim duct
ADUH07LUAS1
ADUH09LUAS1
ADUH12LUAS1
ADUH18LUAS1
ADUH24LUAS1
250 V, 5 A
Activate: 275 ±27°F
(135 ±15°C)
Fan motor stop
Reset: 239 ±27°F
(11 5 ±15°C)
Fan motor restart
― ○
Wall mounted
ASU7RLF1
ASU9RLF1
ASU12RLF1
ASU15RLF1
250 V, 3.15 A
Activate: 221 ±18°F
(105 ±10°C)
Fan motor stop
Reset: 194 ±18°F
(90 ±10°C)
Fan motor restart
― ―
ASUH07LPAS
ASUH09LPAS
ASUH12LPAS
ASUH15LPAS
ASUH18LPAS
ASUH24LPAS
250 V, 3.15 A
Activate: 257±18°F
(125 ±10°C)
Fan motor stop
Reset: 212 ±18°F
(100 ±10°C)
Fan motor restart
― ―
Floor
AGU9RLF
AGU12RLF
AGU15RLF
250 V, 3.15 A
Activate: 302 ±27°F
(150 ±15°C)
Fan motor stop
Reset: 248 ±27°F
(120 ±15°C)
Fan motor restart
Activate: 216°F
(102°C)
―
*: Printed Circuit Board
- 85 -
10. Safety devices
MULTI-SPLIT TYPE
5-unit type
MULTI-SPLIT TYPE
5-unit type

Table of Contents

Other manuals for Fujitsu ASUH07LPAS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASUH07LPAS and is the answer not in the manual?

Fujitsu ASUH07LPAS Specifications

General IconGeneral
BrandFujitsu
ModelASUH07LPAS
CategoryAir Conditioner
LanguageEnglish

Related product manuals