11-3. Combination of external input and output
By combining the function setting of the indoor unit and rotary switch setting of the External input
and output PCB, you can select various combinations of functions.
Combination examples of external input and output are as follows:
Mode
Function
setting
External input
and output
PCB (Rotary
SW)
External input
Indoor unit
Input
External input and output PCB
Terminal Input 1 Input 2 Signal type
0-1 60-00 1
Operation/Stop
(Function setting
46-00)
or
Forced stop
(Function setting
46-02)
Operation/Stop Not available Edge
Operation Stop Pulse
0-2 60-00 2
Forced
Thermostat OFF
Not available Edge
1 60-01 3
Mechanical
cooling Off
2 60-02 4
Forced
thermostat Off
3 60-03 5
Mechanical
cooling On
4 60-04 6
Mechanical
cooling On
5 60-05 7
Forced
thermostat Off
6 60-06 8
Forced
thermostat Off
7 60-07 9
Mechanical
cooling Off
8 60-08 A
Forced
thermostat Off
9 60-09 B
Forced
Thermostat OFF
10 60-10 C
Forced
Thermostat OFF
11 60-11 D
Forced
Thermostat OFF
12 60-12 D
Forced
Thermostat OFF
- 89 -
11-3. Combination of external input and output 11. External input and output (Compact cassette type and slim duct type indoor unit)
MULTI-SPLIT TYPE
5-unit type
MULTI-SPLIT TYPE
5-unit type

Table of Contents

Other manuals for Fujitsu ASUH07LPAS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASUH07LPAS and is the answer not in the manual?

Fujitsu ASUH07LPAS Specifications

General IconGeneral
BrandFujitsu
ModelASUH07LPAS
CategoryAir Conditioner
LanguageEnglish

Related product manuals