13-3. Combination of external input and output
By combining the function setting of the indoor unit and rotary switch setting of the External Input
and Output PCB, you can select various combinations of functions.
Combination examples of external input and output are as follows:
Mode
Function
setting
Rotary
SW
External input
Indoor unit External Input and Output PCB
CN46
1
CN313
2
CN314
0-1 60—00 1
Operation/Stop mode1
(Function setting 46-00)
or
Forced stop mode
(Function setting 46-02)
or
Operation/Stop mode2
(Function setting 46-03)
Operation/Stop Not available
Operation Stop
0-2 60-00 2 Forced thermostat Off
Not available
1 60-01 3
Mechanical cooling
Off
2 60-02 4 Forced thermostat Off
3 60-03 5
Mechanical cooling
On
4 60-04 6
Mechanical cooling
On
5 60-05 7 Forced thermostat Off
6 60-06 8 Forced thermostat Off
7 60-07 9
Mechanical cooling
Off
8 60-08 A Forced thermostat Off
9 60-09 B Forced thermostat Off
10 60-10 C Forced thermostat Off
11 60-11 D Forced thermostat Off
NOTE: Input of Operation/Stop depends on the setting of function setting 46.
00: Operation/Stop mode 1 (Remote controller enabled)
01: (Setting prohibited)
02: Forced stop
03: Operation/Stop mode 2 (Remote controller disabled)
- 131 -
13-3. Combination of external input and output 13. External input and output (LPAS series wall mounted type indoor unit)
MULTI-SPLIT TYPE
5-unit type
MULTI-SPLIT TYPE
5-unit type