Auxiliary equipment control by room temperature
Auxiliary equipment control is switchable by room temperature. Auxiliary equipment switching is per-
formed for each room temperature divided to following 3 zones.
Tr
Ts +0.9°F (0.5 °C)
Ts -0.9°F (0.5 °C)
Ts
Zone C
Zone A
Zone B
Ts: Setting temperature
Tr: Room temperature
Zone Application
When temperature dropping When temperature rising
Primary Auxiliary Primary Auxiliary
A
Both of primary and auxiliary equipment
is unnecessary.
Off Off Off Off
B
Primary heater only.When room
temperature stays in zone B for a long
time, auxiliary equipment also operates.
On
Off*
1
— —
C Auxiliary equipment also operates. On
On*
2
On
On*
2
*1: For standby time for auxiliary equipment operation, refer to indoor unit function number 71 "Con-
tents of function setting" on page 206.
*2: When indoor unit function number 61 is set to "00", auxiliary equipment operates according to the
following conditions.
• Ts - Tr > 21.6 °F (-12.0 °C): Auxiliary equipment turn off.
• Ts - Tr > 18.0 °F (-10.0 °C): Auxiliary equipment turn on.
- 102 -
11-4. Details of function 11. External input and output (Compact cassette type and slim duct type indoor unit)
MULTI-SPLIT TYPE
5-unit type
MULTI-SPLIT TYPE
5-unit type

Table of Contents

Other manuals for Fujitsu ASUH07LPAS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASUH07LPAS and is the answer not in the manual?

Fujitsu ASUH07LPAS Specifications

General IconGeneral
BrandFujitsu
ModelASUH07LPAS
CategoryAir Conditioner
LanguageEnglish

Related product manuals