Outdoor temperature zone
Combination zone
(Heat pump + Heater)
Heater only zone
*A: -4°F (-2C)
A + 3.6°F ( 2°C): -0.F (-18°C)
Outdoor temp.
*: Adjustable by function setting 67
Operation status
Compact cassette type
On
On
12 V
Off
Off
0 V
Heater
Fan
Comp. On/Off
Outdoor temperature
(Factory setting)
Outdoor temperature zone *
Heat pump
prohibition
zone
Combination zone
* The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min.
46.4°F (8°C)
42.8°F (6°C)
-0.4°F (-18°C)
-F (-20°C)
Slim duct type
On
12 V
Off
0 V
Heater
Comp. On/Off
Outdoor temperature
(Factory setting)
Outdoor temperature zone *
Heat pump
prohibition
zone
Combination zone
* The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min.
46.4°F (8°C)
42.8°F (6°C)
-0.4°F (-18°C)
-F (-20°C)
On
Off
On
Off
Fan
DIP-SW101-3 On
DIP-SW101-3 Off
NOTE:
In following operations, compressor will be on in heat pump prohibition zone.
Other than heating
Test run
- 114 -
11-4. Details of function 11. External input and output (Compact cassette type and slim duct type indoor unit)
MULTI-SPLIT TYPE
5-unit type
MULTI-SPLIT TYPE
5-unit type

Table of Contents

Other manuals for Fujitsu ASUH07LPAS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASUH07LPAS and is the answer not in the manual?

Fujitsu ASUH07LPAS Specifications

General IconGeneral
BrandFujitsu
ModelASUH07LPAS
CategoryAir Conditioner
LanguageEnglish

Related product manuals