Indoor unit connect-
ing capacity
Outdoor temperature
Indoor temperature
17.8 °CDB 21.1 °CDB 23.9 °CDB 26.7 °CDB 29.4 °CDB 32.2 °CDB
12.2 °CWB 15.6 °CWB 17.2 °CWB 19.4 °CWB 21.7 °CWB 22.8 °CWB
kBtu/h °CDB TC IP TC IP TC IP TC IP TC IP TC IP
34
-10.0
8.33 1.11 9.41 1.13 9.92 1.14 10.60 1.15 11.36 1.17 11.71 1.17
-5.0 8.33 1.10 9.41 1.12 9.92 1.13 10.60 1.15 11.36 1.16 11.71 1.17
0.0 8.33 1.10 9.41 1.12 9.92 1.13 10.60 1.14 11.36 1.15 11.71 1.16
5.0 8.33 1.22 9.41 1.25 9.92 1.26 10.60 1.27 11.36 1.28 11.71 1.29
10.0 8.33 1.35 9.41 1.37 9.92 1.39 10.60 1.40 11.36 1.42 11.71 1.42
15.0 8.33 1.86 9.41 1.89 9.92 1.91 10.60 1.93 11.36 1.95 11.71 1.96
20.0 8.33 2.37 9.41 2.41 9.92 2.43 10.60 2.45 11.36 2.48 11.71 2.50
25.0 8.33 2.61 9.41 2.65 9.92 2.67 10.60 2.70 11.36 2.74 11.71 2.75
30.0 8.33 2.85 9.41 2.90 9.92 2.92 10.60 2.95 11.36 2.99 11.71 3.00
35.0 8.33 3.04 9.41 3.09 9.92 3.12 10.60 3.15 11.36 3.19 11.71 3.21
40.0 7.24 2.82 8.19 2.87 8.63 2.90 9.20 2.93 9.88 2.96 10.18 2.98
46.1 6.16 2.61 6.96 2.65 7.34 2.67 7.80 2.70 8.40 2.73 8.66 2.75
NOTE:
Specifications are based on the following conditions.
• Power source of specifications: 230 V
• 2 or more indoor units should be connected.
• Pipe length: 24.6 ft (7.5 m), Height difference: 0 ft (0 m) [Outdoor unit - Indoor unit]
• The total ability of connected a indoor unit is from 34,000 Btu up to 54,000 Btu.
• Input in the table are calculated based on the maximum indoor unit input combina-
tions.
- 259 -