¢ Floor/Ceiling type
MODEL: ABYG14LVTA
Outdoor temperature
Indoor temperature (°CDB / °CWB)
18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0
(°CDB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
-10.0 3.26 2.01 3.93 2.45 4.44 2.79 5.01 3.61 5.36 3.95 5.52 4.52
-5.0 3.26 2.01 3.93 2.45 4.44 2.79 5.01 3.61 5.36 3.95 5.52 4.52
0.0 3.26 2.01 3.93 2.45 4.44 2.79 5.01 3.61 5.36 3.95 5.52 4.52
5.0 3.26 2.01 3.93 2.45 4.44 2.79 5.01 3.61 5.36 3.95 5.52 4.52
10.0 3.26 2.01 3.93 2.45 4.44 2.79 5.01 3.61 5.36 3.95 5.52 4.52
15.0 3.26 2.01 3.93 2.45 4.44 2.79 5.01 3.61 5.36 3.95 5.52 4.52
20.0 3.26 2.01 3.93 2.45 4.44 2.79 5.01 3.61 5.36 3.95 5.52 4.52
25.0 3.26 2.01 3.93 2.45 4.44 2.79 5.01 3.61 5.36 3.95 5.52 4.52
30.0 3.26 2.01 3.93 2.45 4.44 2.79 5.01 3.61 5.36 3.95 5.52 4.52
35.0 3.26 2.01 3.93 2.45 4.44 2.79 5.01 3.61 5.36 3.95 5.52 4.52
40.0 3.09 1.80 3.72 2.19 4.20 2.50 4.74 3.23 5.07 3.53 5.22 4.05
46.0 2.91 1.60 3.51 1.95 3.96 2.22 4.47 2.87 4.78 3.14 4.93 3.60
MODEL: ABYG18LVTB
Outdoor temperature
Indoor temperature (°CDB / °CWB)
18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0
(°CDB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
-10.0 4.18 2.50 5.03 3.05 5.69 3.47 6.42 4.49 6.86 4.60 7.07 5.63
-5.0 4.18 2.50 5.03 3.05 5.69 3.47 6.42 4.49 6.86 4.92 7.07 5.63
0.0 4.18 2.50 5.03 3.05 5.69 3.47 6.42 4.49 6.86 4.92 7.07 5.63
5.0 4.18 2.50 5.03 3.05 5.69 3.47 6.42 4.49 6.86 4.92 7.07 5.63
10.0 4.18 2.50 5.03 3.05 5.69 3.47 6.42 4.49 6.86 4.92 7.07 5.63
15.0 4.18 2.50 5.03 3.05 5.69 3.47 6.42 4.49 6.86 4.92 7.07 5.63
20.0 4.18 2.50 5.03 3.05 5.69 3.47 6.42 4.49 6.86 4.92 7.07 5.63
25.0 4.18 2.50 5.03 3.05 5.69 3.47 6.42 4.49 6.86 4.92 7.07 5.63
30.0 4.18 2.50 5.03 3.05 5.69 3.47 6.42 4.49 6.86 4.92 7.07 5.63
35.0 4.18 2.50 5.03 3.05 5.69 3.47 6.42 4.49 6.86 4.92 7.07 5.63
40.0 3.96 2.24 4.76 2.73 5.38 3.11 6.07 4.02 6.49 4.40 6.69 5.04
46.0 3.73 1.99 4.49 2.43 5.08 2.77 5.73 3.58 6.12 3.91 6.31 4.48
NOTES:
• TC: Total Capacity (kW), SHC: Sensible Heat Capacity (kW)
• Values mentioned in the table are based on the following conditions:
– Pipe length: 5 m, Height difference: 0 m [Outdoor unit—Indoor unit]
DESIGN & TECHNICAL MANUAL
- 300 -
OUTDOOR UNIT
AOYG36LBLA5