Fulton Heating Solutions, Inc. -- PHW Manual -- 2010-0713
Page 15
Note
If the rh (Range High) value has been changed in the Input/Output Menu, the Setpoint Temperature
will read zero (0) after return from the menus. Simply press the Up Arrow key until the desired
setpoint value is shown. Hit SET/ENT once to store and begin operation.
Note
At high fire, the gas butterfly valve will be full open in the horizontal position. Exhaust butterfly
valve will be full open in the vertical position.
Note
The unit will still shut off at setpoint plus 5°F (standard settings). Also, being in manual mode, the
temperature control ignores any PID or auto tune settings.
Note
Your Fulton Pulse Combustion Hydronic Boiler has been designed for years of trouble-free
performance. To ensure the continued safety and efficiency of the boiler, the schedule of
maintenance outlined in this section should be adhered to. The boiler should be inspected
annually. All service should be performed by a certified contractor.
Warning
Keep boiler area clear and free from combustible materials, gasoline and other flammable vapors
and liquids.
Note
If for any reason, the air intake or exhaust vent piping is disassembled, reassemble the piping in
accordance with the installation procedure outlined in the installation section of this manual.
Note
Should you suspect that the boilers flue passage ways have become blocked, contact your
recognized Fulton representative.
Note
On models PHW300 through PHW1400 the spark plug is located in the top of the boiler. In
PHW2000 the spark plug is located in the gas injector behind the air flapper, and requires a spark
plug removal tool.