Vers. No. 6.1
82 Released: 25/04/2017
4 Connecting the modules Q.bloxx A116: Connecting sensors
Fig. 4-78 Dialog for shunt activation.
Manual activation
Define the Direction for the variable on Input/output (Fig. 4-
77) and click on Shunt cal. Activate Control
computer in the
dialog (Fig. 4-78).
Setting a value of 16 for the
variable (the channel) activates the
shunt and 0 deactivates it again.
Activation via variable
Click on Shunt cal. Activate At variable value in the dialog
(Fig. 4-78) and specify the variable to be used.
Any variable value > 0.5 activates the shunt.