WIRELESS SITE MANAGER DISPLAYS COMM ERROR FOR A SINGLE
GASMAX/TX
• Network Identifier does not match.
• GASMAX/TX device ID and WSM assigned channel device ID do not match.
• Distance between gas monitor and WSM too great for reliable communications
• WSM beacon not set for SERVER if primary network manager
• Antenna connection compromised or antenna broken.
WIRELESS SITE MANAGER DISPLAYS COMM ERROR FOR ALL GASMAX/TX
• Network Identifiers do not match.
• No synchronizing beacon signal. Verify C2/TX RF Mode = SERVER and verify GASMAX/TX “Server
in Range” icon displayed.
• RF signal attenuated. Check C2/TX WSM antenna connection, cable and remote antenna (if
installed). Place a GASMAX/TX in close proximity with the C2/TX WSM and check for proper
operation.