EasyManua.ls Logo

GE AV-300I - Generic PID; Parameters

GE AV-300I
296 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GEH-6641E
—————— Function Description ——————
168
Ch.1
Use the derivative component as a system damping element, by setting for example:
PD D1 gain % = 1%
PD der filter = 20ms
If it is not required, leave the parameters = 0.
1.16.7 Generic PID
Drive settings: (only those referring to the PID function are described)
Connect to the analog input 1 the reaction signal.
Select PID fbk src = An inp 1 output
Connect to the analog input 2 the reference.
Select PID draw src = An inp 2 output
Connect the feed forward signal to its internal reference.
Select PID inp FF src = Int PID inp FF
Set Int PID inp FF to 100%
Connect to the Digital input 1 the input enabling the PID PI Block
Select PID PI enab src = DI 1 monitor
Connect to the Digital input 2 the input enabling the PID PD Block
Select PID PD enab src = DI 2 monitor
In case just one contact is needed to enable the PI and PD section, it is possible to connect also PID PD enab src
on the digital input 1 as described below.
Select PID PD enab src = DI 1 monitor
Connect to the control variable (Torque, Speed, etc.) the PID output
Select xxxxxxxx src (Torque ref 1 src, Speed ref 1 src, etc.) = PID out s mon; the scale factor of PID out s mon
can be set via the PID Out gain parameter according to the different needs. See chapter 1.1.3, Normalizations
signals.
1.16.7.1 Parameters
Set Full scale spd equal to the motor speed corresponding to 100% of the line speed.
Full scale spd = 2550 rpm
Connect
Mlt PI sel 0 = Null
Mlt PI sel 1 = One The selection of the PID Mlt PI sel 1 multiplier is therefore active.
Set PID Mlt PI sel 1 = 1 The starting value is 1
Set PI lim top e PI lim bot in order to obtain a maximum correction of the PI Block equal to +/- 100% of the
control variable.

Table of Contents

Related product manuals